  Control strategies for extracting the three-phase reference currents for shunt active power filters are compared, uating their performance under different source conditions with PI and Fuzzy Controllers in MATLAB/Simulink environment When the supply voltages are balanced and sinusoidal, the two control strategies are converge to the same compensation characteristics However, the supply voltages are distorted and/or un-balanced sinusoidal, these control strategies result in different degrees of compensation in harmonics. The compensation capabilities are not equivalent, with p-q control strategy unable to yield an adequate solution when source voltages are not ideal. Extensive simulations are carried out with PI controller and also with Fuzzy controller for both p-q and id-iq control strategies under different main voltages.